LEFOO · WATER LEAK DETECTION SENSORS & CONTROLLERS

LEFOO LFLX10 Non-Locating Water Leak Detection Sensing Cable

Manufacturer-listed LEFOO LFLX10 Non-Locating Water Leak Detection Sensing Cable; the detecting cable and the active controller are different system components and require mutually compatible order codes.

Original manufacturer source and option choices

Cable typeNon-locating resistive sensor cable, compatible with LFL10-type alarm panels when configured
Geometry6.0±0.2 mm outer diameter; 2-wire signal path
Resistance/weightOuter conductor resistance ≤0.1Ω/m, 28g/m ±2g/m
Temperature−20 to +75°C
MaterialsHigh-density polyethylene/waterproof spiral cable, yellow PVC skeleton
Fire ratingManufacturer references UL94:2017 V0-like material test; not certification of hazardous area use
Maker length codesBDX for non-locating cable; X03=3m, X05=5m, X10=10m, XDZ custom. Jxx fixing tabs, Yxx lead wire, Zxx termination choices
ExampleBDX X10 J01 Y01 Z01 sample accessory selection

Original LEFOO LFLX10 model and technical source · LEFOO original leakage sensor directory

Original maker source checked 23 October 2026; variant-photo, final device/cable lengths, manufacturer certification, and public HTTP source testing open.

LFLX10 — non-locating two-wire sensing cable

LFLX10 is a resistive, non-locating two-wire water leak sensing cable intended to trigger a compatible alarm controller. The maker’s roughly 6 mm cable diameter and conductor resistance specification are mechanical/electrical inputs, not a certified wet-location enclosure rating for an entire system. Route the cable where water first collects, avoid metal short circuits or chemical contamination, and test with the actual LFL10-compatible panel. It does not encode leak distance like four-core LFLX11.