LEFOO LFH16 Temperature and Humidity Transmitter — Wall, Duct and Split
LEFOO LFH16 Temperature and Humidity Transmitter — Wall, Duct and Split is a specific maker-listed series distinct from similar LEFOO models. Order-code suffixes and electrical/probe interfaces determine actual device ratings.
Maker specification and original ordering-code notes
| Mounting SKU | LFH161 wall, LFH162 duct, LFH163 separated probe |
|---|---|
| Relative humidity | 0–100% RH, ±3% RH at 20°C / 20–80% RH, ±5% elsewhere at same reference temperature |
| Temperature | 0–50°C, −20–60°C and options, ±0.5°C digital at 20°C; RTD grade differs |
| Humidity signal | V10 0–10V (three-wire); A4 4–20mA (two-wire); M RS485/Modbus |
| Power | 15–35VDC or 24VAC ±20% isolated for voltage/RS485; loop-current supply load-dependent 9.5–35VDC (zero load) or 19.5–35VDC at 500Ω |
| Probe/housing | PA6 or optional 304 stainless probe, multiple filter tips, optional LCD; IP65 |
| Original ordering | LFH161 3 A4 A4 1 0 0 1 — illustrative original manufacturer combination |
| Hazardous area | No original model-specific ATEX or IECEx certificate identified |
Original LEFOO LFH16 full specification and order selection source
LFH16 — wall, duct and remote-probe models
The LFH16 family contains LFH161 wall, LFH162 duct and LFH163 separated-probe variations; they are not the same mounting style simply because their electronics are related. Representative location, condensation exposure and probe lead routing control the usefulness of the humidity and temperature values. Compare the manufacturer’s ±3% RH normal-range specification with its wider-environment performance limits, and pair either 4–20 mA, 0–10 V or Modbus variant with the proper supply and BMS points.