WIKA · DIFFERENTIAL PRESSURE TRANSMITTERS

WIKA A2G-50 Differential Pressure Sensor

Original manufacturer WIKA A2G-50 product image
WIKA A2G-50 — original manufacturer’s product/family photograph. Check option-specific geometry.

Air-conditioning and ventilation differential pressure sensing.

Original manufacturer: WIKA

Ex-proof certification: Not established for this model or family in the documentation reviewed. Do not infer hazardous-area safety from a regular HVAC product.

Official Technical Source

Original manufacturer catalog / model documentation →

AirAlign lists the named model or family. Measurement ranges, communication and enclosure options may vary by exact ordering code; check current manufacturer datasheet before specifying a device.

A2G-50 — older analogue/Modbus HVAC transmitter

The WIKA A2G-50 is an established compact piezoresistive differential-pressure transmitter, distinct from the modern A2G-500 platform. It is used on air filters, cleanrooms and HVAC ducts, and instrument options change sensor span, display, zero-point setting and available communication.

TopicOriginal manufacturer detailsImplementation and QA
Output topologySelectable 0–10 V or 4–20 mA, 3-wire; Modbus RTU optionA 4–20 mA loop here does not justify assuming a generic two-wire loop power supply.
Maximum process pressure20 kPa maximum operating pressure per WIKA model pageThis is not the same as the calibrated differential pressure span; avoid exceeding common-mode or port pressure limits.
Measuring rangesMultiple switchable Pa/mbar models, including smaller ±250 Pa and larger 0–12,000 Pa order classesCheck the ordered sensor pressure class and internal scaling jumpers before replacing a device.
Accuracy conditionsWIKA operating manual distinguishes pressure accuracy below/above 125 Pa and separate voltage/current-output errorDo not condense all accuracy components into a universal ±1%; verify the exact variant table.
Power variantsWith autozero: AC/DC 24 V ±10%; other analogue variants have output-dependent supply rangeDo not wire a Modbus or autozero variant using an unverified analogue unit’s power diagram.

Reference documents and exact-variant requirements

Only the stated model/family is compared here. Confirm purchase suffix, pressure port type, zero/span procedure, required supply, output signal, environmental enclosure, individual approvals and photos before final equipment selection. Model numbers, URLs and manufacturer links already on this page are preserved.

OEM sources: WIKA A2G-50 original model data · WIKA A2G-50 configuration shop data.