Vaisala PDT101

Differential pressure transmitter for cleanrooms and air handling systems.

Product Overview

Manufacturer: Vaisala
Product: PDT101
Type: Installed measurement transmitter
Range / measured parameters: Low differential pressure; range varies by model
Communication / outputs: Current or voltage output

Engineering and Selection Considerations

Confirm the exact manufacturer’s ordering code, current availability, calibrated measurement range, output protocol, power supply, operating environment and mounting requirements. Technical parameters can change between models, ordered options or product generations.

Official Technical Documentation

Official manufacturer product information →

Independent AirAlign product reference. Source reviewed 13 October 2026. The manufacturer’s technical documents remain authoritative.

Related Pages

Product category

Vaisala PDT101 — exact range, loop loading and cleanroom selection

Based on Vaisala’s official B211082EN-K (2026) model datasheet, this section distinguishes bidirectional cleanroom pressure transmitters from the unidirectional fan/filter models and the actual analog output configuration.

AttributeOriginal manufacturer dataEngineering note
Available pressure ranges±60 Pa / ±125 Pa (bidirectional), 0–500 Pa (unidirectional); inch-of-water equivalentsChoose model by expected pressure sign and span, not only adjustable zero.
Published accuracy0.4% of full span for bidirectional; 1% of full span for unidirectionalAt very low differential pressure, %span is not %reading.
Response / stability250 ms t10–90; 15-second warm-up; ±0.25% of span/year stabilitySet commissioning zero tolerance and inspection interval.
Current outputTwo-wire 4–20 mA; 12–36 V DC supplyMaximum receiver/loop resistance is (supply voltage minus 12 V)/0.022 A.
Voltage output0–5 V version: 11.5–36 V DC or 24 V AC; 0–10 V: 14–36 V DC or 24 V ACSeparate three-wire voltage output ordering codes from the two-wire current loop.
Connection1/4-inch barbed pressure ports; wall or DIN-rail mounting; detachable terminalsPrevent kinked tubes, leakage, condensation and accidental reversed HI/LO reference.
Ambient / protection−18 to +70 °C; IP40; dry, non-corrosive and non-conducting gas onlyNot weatherproof, washdown-ready or Ex-approved just because it measures pressure.
AdjustmentsFront-access zero ±5% span and span ±3% spanRe-verify calibration after mounting or tubing changes.

Ordering and calibration boundaries

PDT101-P4C is ±60 Pa / 4–20 mA; P4V is ±60 Pa / 0–5 V; P10C is 0–500 Pa / 4–20 mA; P10V is 0–500 Pa / 0–10 V. These are distinct physical orderable versions. The manufacturer’s P10Cx, P10Vx, W10Cx, and W10Vx codes are explicitly listed as not including a calibration certificate. Do not describe every PDT101 as shipped with an individual calibration report.

For a cleanroom differential-pressure cascade, document each room’s reference pressure, alarm direction, tubing route and measured zero at installation. A proof-pressure tolerance of 1 bar means survival of overload, not a calibrated pressure range. Validate loop resistance when connecting a 4–20 mA input through an isolation barrier; pressure readings below nominal detection levels cannot be certified from a generic product catalog alone.

Original technical source: Vaisala PDT101 B211082EN-K technical data (2026). Check revision and part number prior to commissioning.