LEFOO LFT720A / LFT720B Flange Differential Pressure Transmitters
LEFOO LFT720A / LFT720B Flange Differential Pressure Transmitters. Technical family profile based on the original manufacturer’s current model description; options and approvals must be verified against the exact ordered suffix and delivered nameplate.

Manufacturer specifications
| Variants | LFT720A flange-mounted and LFT720B remote-flange types; manufacturer technical catalog treats as separate configuration families |
|---|---|
| Technology | Welded flange/diaphragm oil-filled remote process-pressure transfer based on LFT710 sensing principle |
| Accuracy | Maker current LFT720 website specifies reference accuracy ±0.2% for turndown ≤10, increasing with turndown; original family catalog additionally lists ±0.075% FS for basic chip. Do not conflate reference/process assemblies |
| Outputs | 4–20 mA, 4–20 mA HART, RS485 configurations |
| Environment | IP65, −20 to +70°C ambient with display |
| Ex evidence | Maker advertises ExdIICT6; check exact ATEX certificate and flange/fill combination before safety claims |
LFT720A and LFT720B — flange configuration distinction
LFT720A and LFT720B are listed as flange/remote-diaphragm differential-pressure configurations; the manufacturer’s LFT720B photo should not be used as an exact depiction of LFT720A. Identify one- or two-sided remote seals, fill fluid, capillary length and process flange connection before converting hydrostatic pressure into tank level. Differential error includes thermal effects from seals/capillaries and density differences. Output configuration and Ex approvals require order-specific evidence.
Original technical sources
LEFOO manufacturer model and technical specification · Maker technical downloads
Model-family evidence cross-checked 23 October 2026. Do not infer all orderable variants, historical product availability, or Ex certification from one product overview.