HUBA CONTROL · DIFFERENTIAL PRESSURE TRANSMITTERS

Huba Control 692 Differential Pressure Transmitter

Original manufacturer Huba Control Model 692 product photo
Official Huba Control Model 692 example. Connections and specifications vary by ordered variant.

Differential-pressure measurement in HVAC and industrial applications.

Manufacturer: Huba Control AG.

Ex-proof status: No ATEX/IECEx approval inferred from the ordinary model listing.

Official Source

Huba manufacturer product index / technical documents →

Check measuring range, medium compatibility, output and current approval for the ordered model suffix.

Huba Control Model 692 official current catalog / downloads →

Huba Type 692 — industrial high-pressure differential transmitter

Unlike Huba low-pressure HVAC Types 401/450/699, the Type 692 is a robust ceramic industrial differential-pressure transmitter with process media connections and selectable pressure, material and output configurations. Applications extend to refrigeration, water pumps and industrial process flow.

TopicHuba model specificationEngineering and QA consequence
Pressure measurementDifferential/relative range family 0–25 bar; common system-pressure variants 12, 25 or 50 barThese are BAR-scale pressure classes: not a 0–25 Pa ventilation filter meter.
Dynamics<5 ms response in current Huba model summaryThe actual installed control loop and impulse lines may be slower.
Temperature and materialsMedium/ambient −15…+85°C; Al₂O₃ ceramic sensor, stainless/PVDF/brass process interface choicesSelect seal, housing and port material by the actual process fluid; gas compatibility alone is not enough.
Overpressure/ruptureBursting pressure listed as 1.5× selected system-pressure ratingNever use rupture rating as normal working differential pressure or independent overpressure safety protection.
ElectronicsStandardized signal options selected by 692 ordering code; draw <20 mA per makerVerify supply range and 2-/3-wire signal topology on the chosen 692 configuration drawing.

Variant-specific specification and approvals

Before installing or certifying the device, verify exact Huba order code, system-pressure limits, process media, signal supply, output scaling, pressure ports, EMC and the final assembly’s applicable certificates. No general-purpose ATEX/IECEx approval is claimed on this page.

OEM source: Huba 692 current manufacturer product data.