PRODUAL · CO₂ TRANSMITTERS

Produal RTX-D Touchscreen Room Transmitter

Touchscreen room transmitter; measurement parameters depend on ordered configuration.

Manufacturer: Produal

Ex-proof status: Not established for this exact variant; not advertised here as explosion-protected.

Technical Overview

MeasurementMulti-parameter room sensing
Family / modelRTX-D Touchscreen Room Transmitter

Official Source

Manufacturer source and technical documentation →

Verify current manufacturer datasheet and exact ordered option before using or specifying this model. A manufacturer family page may cover several hardware configurations.

RTX-D — touchscreen depends on ordered sensor set

Produal RTX-D adds a touchscreen room user interface to a multi-parameter transmitter platform, but the installed sensing variables and analog/digital interfaces depend on the supplied code. Verify whether a room project actually needs CO₂, RH, temperature, VOC or fan/space-control functions and document each point’s units. A display and touchscreen do not establish simultaneous availability of every sensor or a certified alarm output. Confirm interface, software revision and mounting before upgrading from a simple RTX room transmitter.

Produal RTX-D — touchscreen room transmitter versus basic RTX — engineering specifications

Original maker documentation distinguishes the ordered hardware’s measured channels, outputs and qualified use cases. Optional feature lists do not establish that every product variant contains every sensor, controller or protocol.

FeatureOEM informationEngineering limits
User interactionConfigurable touchscreen interface for room measurements and controlsTouchscreen commissioning and occupant override are not equivalent to a passive RTX sensor.
Measurement combinationsTemperature, CO₂, RH and other selectable monitored signals by order codeOnly populated sensors/inputs must be shown as present.
BAS communicationRTX-D family supports Modbus RTU, 0–10 V variants; newer BACnet MS/TP availability is documented by OEM in 2026Confirm actual purchased device/firmware and any BTL certificate when specifying BACnet.
I/O capabilityOEM positions RTX-D for display, dual inputs and adjustable temperature setpointIdentify selected input type, control output, and relay or actuator wiring.
Temperature compensationProdual ProTemp and installation quality score are newer room product featuresDo not ascribe firmware feature to older RTX-D without verifying generation.
SetupMyProdual commissioning; some versions need MyTool Connect adapterPlan installer access to site profile, backup of configuration and update permission.
Control logicMay be used for heating/cooling, ventilation and occupancy-related demandAlarm/control interlocks must be engineered for network failure.

Commissioning and application guidance

RTX-D is a user-facing room node and control interface; verify every measured parameter, BACnet/Modbus object or analog channel against the actual full suffix and current firmware. A touchscreen is not evidence that the product always supports a particulate/air-quality gas measurement. For networked buildings, test a lost-BAS connection, reboot behavior and local override arbitration. The OEM’s 2026 materials discuss a BTL-certified BACnet version; do not apply that badge retroactively to earlier Modbus/analog variants.

Original manufacturer: Official model information, technical documents and configurator. Confirm final ordered SKU, supplied options and current data before control or safety-critical use.

AirAlign independent model-specific technical review · 25 October 2026. OEM technical claims are not third-party calibration or Ex/SIL approval.