BAPI Quantum Prime VOC / Temperature / Humidity Sensor

Wall-mounted air-quality sensor with VOC measurement for ventilation demand indication; configurable optional temperature and humidity outputs.

Manufacturer: BAPI

Explosion protection: No Ex certification claimed. Do not treat IP protection or CE marking as ATEX / IECEx approval.

Verified Product Information

MeasurementVOC
MeasurementVOC / CO₂ equivalent per configured variant
MountRoom

Official Manufacturer Source

Open manufacturer model / catalog information →

Electrical specifications, current availability, measurement claims and hazardous-area approvals depend on the actual configuration and revision. Verify the original manufacturer documentation before specifying equipment.

Quantum Prime — VOC-equivalent versus CO₂ measurement

BAPI Quantum Prime is a room IAQ sensor with VOC response and options for temperature/humidity and an inferred CO₂-equivalent value. A CO₂-equivalent derived from VOC or occupancy algorithms is not the same as a calibrated infrared CO₂ concentration, particularly in rooms with solvent sources. Verify the actual suffix’s output channels, sensor scale and control-system interpretation. Place it away from fresh paint and cleaning chemical point sources if the goal is representative building ventilation trends.

BAPI Quantum Prime VOC — CO₂-equivalent is not measured CO₂ — engineering specifications

Original maker documentation distinguishes the ordered hardware’s measured channels, outputs and qualified use cases. Optional feature lists do not establish that every product variant contains every sensor, controller or protocol.

FeatureOEM informationEngineering limits
Chemical sensingMicromachined metal-oxide VOC response converted to an equivalent CO₂ ventilation signalCO₂e 0–2,000 ppm output is a proxy, not a nondispersive-infrared CO₂ concentration measurement.
Input sourcesOffgassing from cleaners, carpets, perfumes, materials and peopleA change in VOC index may occur without any change in actual respiratory CO₂.
Optional channelsTemperature thermistor/RTD and capacitive RH (maker cites ±2%RH family)Only ordered add-on channels are available and need separate BAS point mapping.
Air-quality indicationGreen under 1,000 ppm equivalent; yellow 1,000–1,500; red above 1,500LED thresholds describe VOC-derived equivalent levels, not legal CO₂ limits.
Initial stabilizationManufacturer catalog notes approximately 15-minute startup for VOC moduleVentilation controller should ignore or flag warm-up values.
Response / environmentVOC response under 60 seconds after startup; 0–50 °C, non-condensing RHMetal-oxide temperature/humidity cross-sensitivity requires consistent conditions.
Control interfaceVOC-only or VOC/T/RH/display/override setpoint optionsProduct configurator options determine actual local display and relay/BAS outputs.

Commissioning and application guidance

For demand-controlled ventilation the BAPI CO₂e output can be an occupancy/odor proxy, but do not publish it as a laboratory CO₂ ppm reading or apply CO₂ legal limits to that signal. If a WELL/RESET or building standard requires measured CO₂, specify a genuine optical CO₂ channel in addition. Metal oxide VOC sensing reacts to cleaning agents and building finishes, so commissioning should test ventilation response to cleaning offgassing and long-term algorithm baselines. Verify selected Quantum Prime output wiring and optional T/RH/display/override codes.

Original manufacturer: Official model information, technical documents and configurator. Confirm final ordered SKU, supplied options and current data before control or safety-critical use.