WINSEN · FORMALDEHYDE (HCHO) SENSORS

Winsen ZE08K-CH2O Formaldehyde Module

Winsen ZE08K-CH2O formaldehyde module

Conditioned electrochemical formaldehyde sensor module for HVAC and building IAQ.

Manufacturer: Winsen

Technical specifications

Target gasHCHO / CH₂O
Measurement range0–5 ppm
OutputUART, DAC and PWM (model configuration)
PurposeIndoor-air formaldehyde monitoring

Manufacturer documentation

Official product information / technical documents →

Verify exact gas configuration, part number, calibration, response, environmental limits and applicable safety certification before equipment design-in. Product data can change between revisions. AirAlign is independent of the listed manufacturer.

ZE08K-CH₂O — multiple host outputs

ZE08K-CH₂O is reported with UART, DAC and PWM options and an approximately 0–5 ppm formaldehyde range. Determine which actual outputs are populated or enabled on the ordered module and scale each separately; a UART concentration value is not the same as a calibrated DAC voltage without a defined transfer function. In HVAC systems, ensure enclosure airflow exposes the electrochemical element without persistent condensation. The B and K formaldehyde families differ in range and integration and should not be treated as drop-in substitutes.

ZE08K-CH₂O — five-ppm formaldehyde with analog and UART — technical model review

Source-specific manufacturer specifications, test conditions and practical engineering distinctions. The stated model/range is not a blanket safety approval or a guarantee that related part codes perform identically.

ParameterOEM documentationEngineering interpretation
Gas and chemistryElectrochemical HCHO with temperature compensationDesigned for formaldehyde, not generic all-VOC monitoring.
Factory range0–5 ppm; digital resolution ≤0.01 ppmUnlike ZE08B’s 0–1.6 ppm sensor span.
Power3.7–5.5 V DCDo not wire from 24 V PLC directly.
Output modes3 V TTL UART; 0.4–2 V analog DAC; manufacturer model page also lists 3 V PWMThese are sensor-board I/O, not 4–20 mA industrial transmitter loop.
Warmup / step≤3 min preheat; T90 ≤60 s and recovery ≤60 sDo not equate three-minute initial warmup with sensor response to gas.
Environmental range−20 to +50 °C, 15–90%RH non-condensingDry/wet mechanical protection is needed for suitable ducts.
Nominal operation life5 years in clean air at 18–25 °CNot the ZE08B two-year rating.
InterferenceWinsen identifies alcohol and CO as potential cross-sensitive gasesGas mixture correction and controlled calibration matter.

Installation, electronics and calibration

Select ZE08K where a higher formaldehyde span and local analog/PWM signaling are needed. The 0.4–2 V signal is the manufacturer output for its 0–5 ppm concentration class; confirm analog scaling, ADC input/reference, signal loading and PWM conversion against the specific interface guide. A sensor’s five-year life statement applies to clean air under constrained conditions, not every VOC-rich chemical workshop. If an instrument is being upgraded from ZE08B, validate pin placement, environmental rating, firmware frame and supplier lifespan separately.

Original manufacturer technical source: Official product specifications and primary data sheet. Exact orderable variant, gas and current certificate must govern procurement or any safety function.

AirAlign manufacturer-specific editorial review · 25 October 2026. Detailed integration information is not an independent calibration or Ex/ATEX/IECEx signoff.