WINSEN · CO₂ SENSOR MODULE

Winsen MH-410D

Manufacturer-verified NDIR CO₂ sensor module. Specifications below are taken from Winsen’s official product information.

NDIRCO₂UART · 0.4–2 V analog

Key Specifications

MODELMH-410D
MEASUREMENT TECHNOLOGYNon-dispersive infrared (NDIR)
MEASURED GASCO₂
MEASUREMENT RANGE0–10% vol optional
ACCURACYRange-dependent; see official table
RESPONSE TIMET90 <30 s
PREHEAT TIME3 min
POWER SUPPLY3.6–5 V DC
CURRENT<85 mA average
INTERFACES / OUTPUTSUART · 0.4–2 V analog
OPERATING RH0–95% RH non-condensing
OPERATING TEMPERATURE−20–60 °C
WEIGHT35 g
LIFESPAN>5 years
Specification note: Measurement range and accuracy can depend on the selected variant. Verify the ordered model and current Winsen datasheet before integration.

Product Positioning

Winsen MH-410D is an NDIR CO₂ sensing product from Winsen intended for OEM gas measurement and system integration.

Official Resources

For integration and purchasing decisions, verify the current documentation directly with Winsen.

View Winsen MH-410D Official Page

AirAlign is an independent informational resource and is not affiliated with Winsen. Manufacturer documentation remains authoritative.

MH-410D — percent-volume versus room ppm CO₂

MH-410D is an NDIR module positioned for optional ranges up to 10% CO₂ by volume, unlike ordinary 0–5,000 ppm ventilation sensors. Host software must explicitly map the 0.4–2 V analog signal or UART data to correct engineering units and ordered range: 1% volume CO₂ equals 10,000 ppm. The accuracy varies by range and calibration. Confirm power supply, sampling gas composition, preheat and seal/optical contamination requirements; a high-concentration chamber measurement should not automatically be treated as a life-safety alarm.

Winsen MH-410D — industrial percent-volume CO₂, analogue 0.4–2 V — engineering selection and model documentation

The published manufacturer values below are bounded to their orderable range, test conditions and actual interface, not general guarantees about every relative in the same sensor family.

ParameterManufacturer evidenceEngineering boundary
Measurement classNDIR CO₂ for percent-volume industrial gasDistinguish %vol high-concentration control from 400–2,000 ppm room ventilation.
Order rangeIndustrial family rated to 0–10% vol by selected sensor; 10%vol equals 100,000 ppmDo not treat the entire 10%-vol option as an IAQ-grade 1ppm resolution span.
Output hardwareUART serial and 0.4–2 V analogue output documented by makerAn analogue voltage signal is not a 4–20mA passive loop or native BACnet.
Supply / environment3.6–5.0 V DC; −20 to +60 °C; 0–95%RH noncondensingThe sensor itself cannot be powered from a 24 V BAS line.
Sensor lifeManufacturer quotes >5-year designed operating lifeCheck drift and original reference-gas validation, especially at high concentration.
StartupOriginal model page describes ~3-minute preheatBlock early values and consider downstream tubing lag.

System integration and calibration

Because 0–10%vol CO₂ is a high process-gas level, the sensor should not be described as an occupancy indicator with the same error budget as compact 2kppm units. If selected for biogas or fermentation, verify pressure, carrier-gas interference, sample-path contamination and humidity. A correctly displayed percent CO₂ level does not measure oxygen depletion directly: use independent oxygen/personal safety instrumentation. Controller decoding of the 0.4–2V analogue mode must use its exact ordered full-scale, not a generic 0–5V input scale.

Source and exact-order documentation: Original manufacturer catalogue, page and/or technical data sheet. Any version- or test-bound claim must be checked against the supplied production label before procurement.

AirAlign model-specific technical editorial update · 25 October 2026. These OEM values are not independently calibrated, certified, or evidence of active supplier stock.