SENSEAIR · CO₂ SENSOR

Senseair Sunrise

Manufacturer-verified NDIR CO₂ sensor or OEM sensor module. The specifications below are based on the manufacturer’s official product information for the displayed reference.

NDIRCO₂I²C · UART

Key Specifications

REFERENCE / MODEL006-0-0008
MEASUREMENT TECHNOLOGYNon-dispersive infrared (NDIR)
MEASURED GASCO₂
MEASUREMENT RANGE0–10,000 ppm
ACCURACY±30 ppm ±3% of reading
RESPONSE TIME30 s
WARM-UP TIME0 s
POWER SUPPLY3.05–5.5 V
CURRENT125 mA peak · 1–34 μA average
COMMUNICATIONI²C · UART
OUTPUTSDigital
OPERATING RH<85% RH
OPERATING TEMPERATURE<50 °C
DIMENSIONS33.5 × 19.7 × 11.5 mm
WEIGHT5 g
LIFE EXPECTANCY>15 years
Specification note: Values shown here correspond to the displayed manufacturer reference. Check the latest official specification for complete conditions, variants and integration requirements.

Product Positioning

Senseair Sunrise is part of SENSEAIR’s NDIR CO₂ sensing portfolio. AirAlign keeps this page focused on manufacturer-published specifications so products can be compared without mixing unverified reseller data.

Official Resources

For design-in, calibration, compliance and purchasing decisions, verify the current documentation directly with SENSEAIR.

View Senseair Sunrise Official Page

AirAlign is an independent informational resource and is not affiliated with SENSEAIR. Specifications can change; manufacturer documentation remains authoritative.

Senseair Sunrise — ultra-low-power non-dispersive infrared sensor

Original Senseair documentation identifies concrete product codes and operating conditions. Accuracy, power, communications and calibration claims below are restricted to the specified variant.

Engineering itemManufacturer valueDesign meaning
Official product order006-0-0008 NDIR CO₂ moduleConfirm variant before comparing with Sunlight article 006-1-0100.
Published range/accuracy0–10,000 ppm; ±(30 ppm + 3% measured CO₂)At 1,000 ppm published numeric expression implies about ±60ppm.
Energy architecture3.05–5.5 V; roughly 1–34 µA average depending on sample cadence; 125 mA measurement peakAverage microamp rating requires duty-cycled operation, not continuous 125mA draw.
Host interfaceI²C or UART digitalDo not connect TTL/UART pins to 24V PLC or assume physical RS485.
Response/startup0-second declared warmup and ~30s gas responseWake-up ability does not imply immediate equilibrium after a gas step.
Integration shape33.5 ×19.7 ×11.5 mmFootprint and connector are not identical to Sunlight despite family relationship.
Calibration environmentAutomatic baseline correction available; Dual Technology edition offered for continuously occupied spacesChoose Dual Technology where periodic outdoor CO₂ exposure cannot be guaranteed.

Application, firmware and calibration considerations

The Sunrise is optimized for battery-operated and intermittent-reading wireless IAQ nodes. The correct energy budget includes ~125mA peaks during NDIR emission plus the standby/sampling interval. Beware using automatic self-calibration in sealed, always-occupied rooms or CO₂-enriched mushroom farms. Senseair explicitly markets a Dual Technology variant to address some 24/7 occupied applications; confirm this is the supplied version rather than assuming its calibration logic exists in the base article number. The low-power device cannot independently satisfy a hazardous-atmosphere personal gas alarm.

Official model source: Senseair product model, technical specification and version list. Regionally older catalogs may differ; the actual ordered revision and reference procedure control final procurement and calibration.

AirAlign model engineering note · 25 October 2026. OEM specifications are not independent finished-device conformity, clinical measurement approval or active stock confirmation.