Products & Manufacturers / CO₂ NDIR module
CFSensor XGZG360M
Manufacturer: CFSensor. Products & Manufacturers
CO₂ NDIR module. Values below are manufacturer family specifications; ranges and options differ by ordering code.
Technical specifications
| Gas | Carbon dioxide (CO₂) |
|---|---|
| Technology | NDIR |
| Standard measurement range | 400–5,000 ppm |
| Digital output | UART |
| Accuracy | Check current manufacturer datasheet for ordered version |
Official technical documentation
Manufacturer technical source / datasheet ↗
Source reviewed: 17 October 2026. Exact SKU specifications, certifications and ordering options must be verified before product selection.
XGZG360M — NDIR CO₂ UART module
XGZG360M is a compact CO₂ sensing module listed around 400–5,000 ppm, with UART output rather than a direct industrial 4–20 mA loop. The host firmware must implement the manufacturer’s serial frame, timing and error handling, and distinguish fresh measurements from retained readings during warm-up. Confirm optical sampling airflow, automatic baseline correction assumptions and deployment at consistently elevated CO₂. The sensor module itself is not an independently certified whole-room alarm or ventilation controller.
XGZG360M — 2023 NDIR CO₂ UART protocol, electrical peaks and ASC — original technical reference
Model-specific measurement and electrical figures, output options and their source limitations.
| Measured feature | Maker data | Practical engineering implications |
|---|---|---|
| Optical principle | NDIR CO₂ with temperature correction and digital output | Not calculated CO₂ equivalent from VOC; component alone not finished monitor. |
| Calibrated span | 400–5,000 ppm standard, 10,000 ppm optional by order | Do not assume 10,000-ppm accuracy on all standard units. |
| Accuracy | ±(50 ppm + 5% of measured value) at 25 °C in sheet V1.3 | At 1,000 ppm approximately ±100ppm manufacturer formula, pressure corrections additional. |
| Response vs sampling | 2-second output interval, <30 s initial preheat, best accuracy after about 4 minutes | The source prints response-time ‘≤2 ppm’ (wrong units); do NOT assert a response T90 in seconds from that erroneous field. |
| Power supply | 4.9–5.5 V DC; ripple ≤35mV and source current capacity ≥500mA | Optical emitter pulses can be about 110mA even when average ~25mA. |
| Digital protocol | TTL UART 9600-8N1 with Modbus 0x04 function / CRC16 over the UART wiring | Modbus framing does not imply a direct physical RS485 port on all variants. |
| Options | PWM and 0–2 V outputs listed as custom order choices | Check PTX/PRX, Aout and PWM connection pins on actual PCB. |
| Autocalibration | Default clean-air baseline cycle around 48 hours, typical 400 ppm reference assumption | A constant high-CO₂ mushroom room can cause wrong fresh-air baseline if conditions are unmet. |
| Durability | −10 to +50 °C operation, ≥10-year maker design life | Calibrate and monitor drift rather than inferring no upkeep. |
System selection and verification
The original February 2023 specification gives a particularly useful host example: a command 01 04 reads the CO₂ register using Modbus-style framing and CRC over the TTL UART, with 0x0258 decoded as 600 ppm. For 24/7 CO₂-enriched agricultural spaces, the self-calibration scheme can falsely anchor to non-outdoor air; set a documented manual reference instead, and note the OEM recommends annual digital calibration. The published datasheet calls its response time ‘≤2 ppm’ for a 90% step, an obvious dimensional inconsistency. Do not convert this to ≤2 seconds or repeat it as a verified performance limit.
Primary official specification: Model manufacturer technical documentation. Order suffixes, current revisions, traceable calibration and certifications are subject to final confirmation.
AirAlign manufacturer-specific editorial enhancement · 25 October 2026. Not independent source calibration, site regulatory signoff or finished-safety-instrument certification.