General Life GAIA HT110S
GAIA HT110S is a General Life room thermostat. This profile documents the wired version’s published technical data and keeps other manufacturer-listed configurations separate.
Model Identification
Manufacturer: General Life
Series: GAIA
Model: HT110S
Category: Room thermostat
Key Specifications — GAIA HT110S (Wired)
Related Pages
Official Resources
Source: General Life’s GAIA HT110S wired product specification. Technical data checked on 11 October 2026.
Official GAIA HT110S Wired Product PageAirAlign is an independent informational resource.
Model selection and commissioning — GAIA HT110S
Dimensions and supply: GAIA HT110S has a manufacturer-listed 85mm / 125mm / 24mm housing (landscape-style). Room-unit supply is 3V DC (2 x AAA Alkaline Battery). Verify wall coverage, cable exit, battery accessibility and clearance from sources of hot/cold air before mounting.
Relay compatibility: The exact wired profile gives 2A/30VDC (Resistive Load) 0.5A/125VAC (Resistive Load) for the normally-open contact. These resistive ratings cannot be used as a universal motor/boiler starting-current rating. Identify the heating unit’s voltage-free versus powered thermostat input and the correct contact circuit before connection.
Control setup: The recorded room setpoint band is (5°C) – (35°C); operating sensitivity is 0.3°C. Distinguish the stated control sensitivity from display increments and the accuracy of the installed temperature measurement. Confirm heat-source cycling response and suitable room placement.
Not interchangeable by name: A sibling GAIA HT110S RF or SMART configuration can use a separate receiver or different control interface. Do not infer its voltage or programming functions from this wired model. The linked original General Life page remains the source for the exact revision.