Prosense SafeVader Indoor Gas Detector Series

Continuous LEL, toxic, oxygen and VOC monitoring range designed for safe-area indoor installations, with LCD interface and cloud-linked options.

Manufacturer: Prosense

NOT MARKED EX-PROOF

SafeVader source explicitly describes safe areas/indoor applications; do not assume suitability for classified hazardous zones.

Applications & Integration

Used in fixed industrial or indoor gas monitoring systems with detector variants selected by target gas, measurement range, instrument output and installation requirements. This is a detector product family, not a bare OEM sensor component.

Official Manufacturer Documentation

Prosense official SafeVader Indoor Gas Detector Series source →

Ex markings are not inferred from other Prosense products. These series records are not a substitute for product-specific approvals or installation manuals.

SafeVader — detector sensor module and output matching

Selection pointModel-family evidence
Measured gases and sensor optionsManufacturer offers IR, catalytic, electrochemical, PID and semiconductor modules for applications involving LEL, oxygen, toxic gases and VOC. The selected sensor cartridge determines range and performance.
Electronics and supply12–28 VDC (24 V nominal) and 128×64 LCD on listed family versions; analog 4–20 mA and RS485 Modbus RTU interface options.
Relay outputsListed detector family uses two adjustable alarm contacts and one fault relay; actual relay load at 1.25 A / 30 VDC. Wire contactors rather than powering large motors directly.
EnvironmentABS housing and IP54; maker lists −20…+60°C and non-condensing humidity limits with model-dependent notes.
Lifecycle and cloudLocal menu supports setpoints, module replacement and bump/function tests. Cloud reporting is described through compatible Prosense DPX panels rather than as a guaranteed stand-alone cellular modem.
Hazardous-area restrictionManufacturer explicitly describes SafeVader as a safe-area indoor device; flameproof and intrinsic-safety claims for Prosense’s other detectors must not be transferred.

Do not mix 4–20 mA and Modbus alarm semantics, and do not treat a bump test as a documented calibration. Choose an actual SV-xxxx gas suffix, check the approved sensor module and certified detection-system design.