Prosense P-3212PEK Petrol vapour Gas and Impact Detector

The Prosense PE-KAYO P-3212PEK is a fixed catalytic gas detector for Petrol vapour combined with a three-axis impact sensor. The manufacturer targets fuel filling stations and related installations.
Manufacturer: Prosense.
Manufacturer-marked II 2G Ex db IIC T5 Gb; Zone 1–2; ATEX IMQ 19 ATEX 045 X; IECEx IMQ 18.0009X. Approval applies to certificate-scoped variants only. Check marking on delivered instrument.
Technical Details
| Gas / Model | Petrol vapour · P-3212PEK |
|---|---|
| Gas measurement | 0–100% LEL, catalytic |
| Impact measurement | Three-axis accelerometer |
| Signal outputs | 4–20 mA analog; Modbus RS485 described in company datasheet |
| Environment | IP65 enclosure; −40 to +70°C per manufacturer |
Official Primary Source
Prosense PE-KAYO exact model list → · PE-KAYO manufacturer datasheet (English PDF) →
Image provenance: A representative Prosense detector image is now displayed from the manufacturer’s own PE-KAYO product-gallery page. The source filename is generically P-series, and no individual gas code is legible, so treat it as series representative, not exact SKU photograph.
Primary Ex documentation: EU-Type certificate IMQ 19 ATEX 045 X in Prosense manufacturer manual → · P/PE/PEK/PES manufacturer declaration →. Confirm exact approved variant and issue status.
Archived and current model-name crosswalk
Prosense’s 2020 PE-KAYO specification table explicitly identifies the petrol vapour model code P-3212PEK; the current English PE Kayo catalog lists PE KAYO-3212 for the same gas description. These are source-level naming records, not proof of unrestricted revision or accessory interchangeability. Resolve the delivered order code, gas calibration, label and certificate issue with Prosense before replacement or procurement.
Petrol-vapour detection versus a defined fuel gas
The historical P-3212PEK is listed in Prosense’s archived catalog for petrol vapour and motion/impact monitoring. Petrol vapour is a variable hydrocarbon mixture, so the applied calibration and LEL alarm interpretation must follow Prosense’s named model and the actual installation, not a propane or methane setting chosen because the unit looks identical. At a filling station, potential vapour release paths, ventilation and fuel-handling equipment influence detector positioning. The three-axis impact function, gas 4–20 mA reading and any Modbus communications are separate alarm-system signals and must be commissioned accordingly. Historical and current product names do not independently prove certificate scope for a substituted unit.