LEFOO · AIR QUALITY MONITORS & GAS DETECTORS

LEFOO LFG60 All-in-One Air Quality Transmitter

LEFOO LFG60 All-in-One Air Quality Transmitter with optional LCD display
Original manufacturer’s display-equipped indoor LFG60 version. LEFOO also offers non-display/top-suction variants. Model/photo source.

Multi-parameter indoor air quality transmitter; confirm target sensors and exact SKU.

Manufacturer: LEFOO

Measurement: IAQ parameters

Ex-proof certification: Not claimed for this item. Do not confuse IP rating or CE conformity with hazardous-area approval.

Official Documentation

Official manufacturer product information →

Measurement range, output options, current revision and compliance must be checked against the exact manufacturer datasheet. Family listings do not establish specifications for every configured SKU.

LFG60 — multi-pollutant IAQ channel definitions

An all-in-one air-quality transmitter may combine multiple sensing principles, so each channel’s detection range, unit, accuracy and service life must be verified separately on LFG60’s exact configuration. The pictured display/top-suction variants are not identical installations. BMS integration must distinguish measured CO₂, temperature, RH and any inferred VOC/IAQ index. A combined module cannot automatically supply a regulatory-grade particulate or toxic-gas alarm.

LFG60 — seven IAQ channels with different physics and timing — engineering details

Hardware output variants, sensor channels and the original maker’s rated operating environment must be matched with the actual supplied part number.

Technical parameterOriginal manufacturer dataApplication consequence
ChannelsUp to temperature, RH, CO₂, PM2.5, PM10, VOC and formaldehydeUp to seven measured parameters: different sensors, warmups and accuracy terms.
CO₂NDIR 0–5,000 ppm, ±(40 ppm + 3% of measured value), T90 ~2 minSeparate CO₂ ppm from a VOC metal-oxide reading.
PMLaser optical PM2.5 0–500 µg/m³; PM10 0–600 µg/m³Dust accumulation and fog can bias optical mass; verify representative airflow.
VOCMOX gas sensing 0–2 ppm; first startup about 1 hour and subsequent 3-minute warmupVOC signal is not compound-specific worker exposure measurement.
FormaldehydeElectrochemical HCHO 0–1 ppm; ±10% FS at 25 °CHCHO is its own gas channel and requires selective calibration.
Temp/RH0–50 °C typically ±0.5 °C at 20 °C; RH 0–100% with typical ±3%RHEach channel’s response and uncertainty should be logged separately.
Power and bus12–36 V DC / 24 VAC ±20%; isolated or non-isolated Modbus RS485Use isolated AC supply per maker note, proper terminal assignment and device addressing.
Physical designIndoor or top-suction versions; IP30, optional LCD and status LEDsIP30 is not a weather-protected rooftop sensor.

Commissioning and maintenance

Treat each of the seven channels as independent input and alarm type. A single air-quality LED cannot replace traceable CO₂ ppm, selective formaldehyde ppm or particulate mass. The VOC sensor requires a much longer first power-on preheat than the quick PM response, so BAS commissioning should tag startup validity by channel. For a school or airport, verify Modbus addressing, installation airflow, PM dust servicing and HVAC control fail-safe. A combined device does not create a certified personal hazardous-gas alarm.

Original manufacturer source: LEFOO exact model product specifications. Exact variant documentation must govern installation and certification.

AirAlign product-level technical review — 25 October 2026. Independent safety/Ex/product warranty validation still pending.