HONEYWELL · CO₂ SENSOR

Honeywell CRIR E1

A commercial single-channel NDIR CO₂ sensor designed for indoor air quality and ventilation applications, with UART/Modbus communication and automatic baseline correction.

NDIRCO₂UARTModbus

Key Specifications

MEASUREMENT TECHNOLOGYSingle-channel non-dispersive infrared (NDIR)
MEASURED GASCO₂
STANDARD RANGE400–2,000 ppm; up to 5,000 ppm extended
ACCURACY±50 ppm ±5% of reading
RESPONSE TIME<120 s (T90)
MEASUREMENT INTERVAL4 s
POWER SUPPLY4.5–5.5 V
POWER CONSUMPTION300 mA peak · 30 mA average
COMMUNICATIONUART · Modbus protocol
OPERATING TEMPERATURE0–50 °C
OPERATING HUMIDITY0–90% RH, non-condensing
DIMENSIONS33 × 22 × 11.2 mm
WEIGHT<8 g
EXPECTED OPERATING LIFE10 years

Product Positioning

CRIR E1 is designed for normal IAQ applications and incorporates Automatic Baseline Correction to support long-term stability in occupied-space monitoring.

Official Resources

Specifications on this page are based on current Honeywell manufacturer documentation. Verify the latest datasheet and user guide before integration or purchasing decisions.

View Honeywell CRIR Official Page

AirAlign is an independent informational resource and is not affiliated with Honeywell. Manufacturer documentation remains authoritative.

Honeywell CRIR E1 — economy NDIR with greater CO₂ uncertainty — engineering selection and model documentation

The published manufacturer values below are bounded to their orderable range, test conditions and actual interface, not general guarantees about every relative in the same sensor family.

ParameterManufacturer evidenceEngineering boundary
Measured gasSingle-channel infrared NDIR carbon dioxideNot a VOC-estimated eCO₂ output.
E1 accuracy grade±(50 ppm +5% of reading)At 1,000 ppm approximate combined nominal error ±100 ppm, larger than M1.
M1 comparisonM1 ±(40 ppm +3% of reading)For tight ventilation thresholds, evaluate absolute error at operating setpoint.
E1 range400–2,000 ppm standard; up to 5,000 ppm extended on existing order specificationHigher 10k ppm extended value appears for M1, not generic E1.
Digital dataUART/Modbus protocol, ~4-second update in original technical contentPhysical UART should not be connected as native industrial 2-wire RS485.
Power and environment4.5–5.5 V; 300mA emission peak/~30mA average; 0–50°C and noncondensing indoor RHPeak is critical to Wi-Fi battery nodes and regulator drop.
CalibrationABC automatically targets 400ppm minimum over adjustable periodA permanently occupied hospital/process room could require a different calibration strategy.
Current OEM documentsHoneywell lists separate February 2026 E1 datasheet and user guideSelect the purchased article’s datasheet, not M1 pin/accuracy tables.

System integration and calibration

E1 can be an economical indoor demand-control CO₂ module, but its percent-of-reading and fixed ppm error make it less suitable for certain stringent reference targets than CRIR M1. As with other ABC-calibrated single-channel infrared sensors, repeated outdoor-level exposure must be credible in the installed location. Alarm/ventilation thresholds should include absolute uncertainty at 1,000–2,000ppm. Source version labels, UART baud/configuration, pullups, reset timing and measurement-ready status should be commissioned on the real hardware. Finished fire/gas safety approval is outside this component listing.

Source and exact-order documentation: Original manufacturer catalogue, page and/or technical data sheet. Any version- or test-bound claim must be checked against the supplied production label before procurement.

AirAlign model-specific technical editorial update · 25 October 2026. These OEM values are not independently calibrated, certified, or evidence of active supplier stock.