PROSENSE · AIR QUALITY MONITORS & GAS DETECTORS

Prosense S-DPX004 Analog Gas Control Panel

Gas monitoring control panel supporting up to 4 analog 4–20 mA channels, MODBUS RS485, event logging and alarm relays.

Manufacturer: Prosense

Certification / explosion protection status: EX-PROOF NOT ESTABLISHED

Panel certification and its installation location must be evaluated separately from Ex-rated field detectors.

Official Technical Source

Prosense official product information →

Confirm active production, variants, wiring and exact certifications with the manufacturer. AirAlign does not independently certify safety systems.

S-DPX004 — four analog loops and alarm relays

Prosense specifies four 4–20 mA analog detector inputs, a visible OLED screen, 500 logged events and configurable alarm/fault/overrange dry-contact relays for S-DPX004. The four analog input channels are not equivalent to the digital RS485 detector input capacity of an S-DPX128; Modbus output to a supervisory platform does not add 128 field input channels.

At commissioning, record detector gas identity and scaling (ppm, %LEL or %vol) for each input. Prove open-circuit fault, Alarm 1/2/3, overrange and power-loss behavior separately before connecting shutdown or ventilation interlocks. The enclosure rating or an Ex-certified detector on the input does not automatically make the control panel suitable for installation in an explosive atmosphere. The exact model certificate, installation location and commissioning manual govern.

Primary model source: Official manufacturer specifications. Certification, installed wiring and supplied revision remain subject to final order-code QA.