BAPI Digital CO & NO₂ Sensor
Multi-gas parking-garage / equipment-area sensor for CO and NO₂ with digital BAS communications.
Manufacturer: BAPI
Verified Product Information
| Measurement | CO and NO₂ |
|---|---|
| CO range | 0–500 ppm |
| NO₂ range | 0–20 ppm |
| Output | BACnet MS/TP or Modbus RTU (field configurable) |
Official Manufacturer Source
Open manufacturer model / catalog information →
Electrical specifications, current availability, measurement claims and hazardous-area approvals depend on the actual configuration and revision. Verify the original manufacturer documentation before specifying equipment.
BAPI Digital CO & NO₂ — two independent parking-garage hazards — engineering specifications
Original maker documentation distinguishes the ordered hardware’s measured channels, outputs and qualified use cases. Optional feature lists do not establish that every product variant contains every sensor, controller or protocol.
| Feature | OEM information | Engineering limits |
|---|---|---|
| Target gases | Carbon monoxide 0–500 ppm; nitrogen dioxide 0–20 ppm as selected sensing elements | Two gases require different alarm setpoints; never scale NO₂ using a CO 500-ppm BACnet point. |
| Mounting options | Duct probe or rough-service wall/beam enclosure | Select sensor exposure and service access based on garage exhaust/traffic pattern. |
| Bus choices | Field-configurable BACnet MS/TP or Modbus RTU | Configure RS485 address, baud/parity, bus termination and BAS object mapping. |
| Other channels | Optional temperature and relative humidity | A gas-only model does not automatically provide calibrated RH/temperature. |
| Self-check and maintenance | Maker indicates daily element self-test and approximately seven-year nominal element life | Automatic electrical test cannot replace span gas verification or gas-response testing. |
| Certificates | Original vendor offers electronic CO and NO₂ calibration certificates on request | Calibration paperwork and real-time post-installation acceptance are distinct. |
| Application | Parking structures, warehouses, equipment spaces | Maintain alarm-to-fan/ventilation interlocks and fail-safe BACnet loss response. |
Commissioning and application guidance
Build the parking garage BAS schedule with separate CO ppm and NO₂ ppm point names, thresholds and escalation stages. The ordered part determines installed elements and modbus priority register mapping; optional temperature/RH changes sensor order and address locations. Check the actual wiring manual and stop bits rather than guessing a universal fixed register layout. Self-test refers to on-board element diagnostics; a periodic span gas functional check remains important. BAPI’s device is an air-quality/control sensor, not proof that the complete parking-garage emergency ventilation system meets a regional safety standard.
Original manufacturer: Official model information, technical documents and configurator. Confirm final ordered SKU, supplied options and current data before control or safety-critical use.
AirAlign independent model-specific technical review · 25 October 2026. OEM technical claims are not third-party calibration or Ex/SIL approval.