BD|SENSORS · DIFFERENTIAL PRESSURE TRANSMITTERS

Products & Manufacturers / Differential pressure transmitter

BD|SENSORS DPS 200

Manufacturer: BD|SENSORS. Products & Manufacturers

Differential pressure transmitter. Values below are manufacturer family specifications; ranges and options differ by ordering code.

Technical specifications

Pressure range 6–1,000 mbar (model options)
Accuracy 2% FSO
Sensor Silicon
Application HVAC

Official technical documentation

Manufacturer technical source / datasheet ↗

Source reviewed: 17 October 2026. Exact SKU specifications, certifications and ordering options must be verified before product selection.

DPS 200 — economical HVAC differential monitoring

DPS 200 is listed for HVAC-type differential pressure monitoring with 6–1,000 mbar variants and a nominal 2% FSO class. Determine whether that full-scale uncertainty is acceptable at the actual fan/duct pressure drop, especially when range is oversized. For filter condition monitoring, verify high/low hose connections, zero procedure and enclosure exposure. This transmitter is not an independent safety-rated fan-pressure proving switch, nor should DPT 200 precision claims be copied across to it.

DPS 200 — economical HVAC differential pressure control: technical profile and specification boundaries

Original BD|SENSORS catalogue differentiates calibrated pressure ranges, media and approval tiers. A family range and optional certification must not be confused with the ordered device.

Parameter Original maker statement Practical selection note
Primary duty Duct/fan/filter monitoring for HVAC gas pressure differences Not a wet/wet hydrostatic level probe or precision process cell.
Range portfolio From 0–6 mbar to 0–1000 mbar depending on model Select range by expected normal and alarm differential.
OEM accuracy 2% FSO Distinguish full-scale error from ±2% of individual low-flow reading.
Transducer Piezoresistive silicon differential sensor Requires dry non-aggressive air/gas and proper tube routing.
Compliance listing BD|SENSORS catalogue shows CE and UL markers No automatic ATEX/IECEx certification just from these badges.
Industrial network Standard listing does not claim universal BACnet/Modbus outputs Use the specified device’s output variant, analog PLC wiring and settings.
Application risk Filter clogging and fan-proving thresholds require directional ΔP and fault detection Do not use an uncertified HVAC pressure input as the sole safety interlock.

Application engineering and commissioning

For a filter-pressure alarm, establish baseline pressure across a clean filter at a defined airflow and choose a differential span near expected dirty-filter cutoff. At 2% FSO, an unnecessarily high-range DPS 200 might have a large absolute measurement uncertainty near a low threshold. Compare DPS 200 against DMD 341 higher-accuracy variants before selecting for tight cleanroom pressurization. Properly secure impulse tubing; avoid condensate pockets and pneumatic leaks, and provide clear wiring-failure indication.

Original product range: BD|SENSORS manufacturer specifications and linked model documentation. Review exact current sensor code, output, material and certificates before final purchasing.

AirAlign independent technical editorial enrichment · 25 October 2026. These statements are not standalone Ex-area approvals, calibration certificates or proof of active stock.