EBTRON · THERMISTOR THERMAL DISPERSION

EBTRON HTx116-P

Multipoint airflow measuring system for ducts and plenums.

Technical Profile

Primary measurement technologyMultipoint thermistor thermal dispersion
Measurement rangeConfiguration dependent; refer to manufacturer
Outputs / communicationsAnalog / BACnet / Modbus options, model dependent

Selection Notes

Check the exact ordering code and manufacturer specifications for accuracy, calibration, probe geometry, supply voltage, permitted environment, signal mapping and installation clearances. Do not assume all variants share the same interface or range.

Manufacturer Profile

View EBTRON on AirAlign →

Manufacturer Source

Official product information and technical documents →

← Browse Air Velocity Transmitters

AirAlign independent technical reference. Model family and variant-specific specifications should be confirmed from the linked manufacturer source before purchase.

HTx116-P — distributed multipoint air measurement

Unlike a single-point duct velocity probe, the EBTRON HTx116-P measures an airflow field through a multipoint arrangement for ducts/plenums. Select array dimensions and insertion pattern to capture the actual cross-section and flow nonuniformity. Match the intended analog/BACnet/Modbus variant to the BMS; verify how the transmitter calculates/averages velocity and volume flow. Calibration, sensor count and installation clearances should be documented separately; a plenum array cannot be replaced with a single pitot tube on model-name similarity.

EBTRON HTx116-P — multipoint thermal-dispersion measurement array — verified technical selection

Source-specific engineering data for the model and its defined variant. All specifications are maker statements and are not an independent AirAlign test or approval.

ParameterManufacturer specificationPractical limitation
Sensing arrangementHigh-density multipoint calibrated bead-in-glass thermistor sensor nodesUnlike single-point pitot/thermal insertion probes, this measures a velocity profile over a duct cross-section.
Calibrated airflow speed0–5,000 FPM (0–25.4 m/s)Not necessarily a guarantee of stable performance when a duct is severely obstructed.
OEM stated flow precision±2% of reading to NIST-traceable airflow standards, including transmitter uncertaintySpecified calibrated node performance is not an unconditional installed whole-duct accuracy in all geometries.
Calibration density16 flow calibration pointsRetain calibration and probe array spacing documentation.
Temperature accuracy±0.15 °F / ±0.08 °C velocity-weighted average, 3 temperature pointsTemperature is flow-weighted at sensor nodes, not a separate absolute room thermometer.
Calibrated air temperature−20…+160 °F (−28.9…+71.1 °C)Probe calibration envelope differs from electronic housing environmental limits.
BAS/network familyBACnet/Modbus restricted to HTB116e, HTM116e, HTS116e, HTC116e per makerDo not claim all HTx116-P transmitters have native digital BAS connectivity.
Probe assemblyGold-anodized aluminum tubes, 316 stainless option, separate mounting arrangementsSelect support/grid density and probe length based on duct geometry.

System integration and commissioning

Multipoint arrays help characterize uneven duct and plenum profiles, but their performance still relies on the real installation envelope, correct probe depth, bracket orientation and airflow model. EBTRON offers standoff, internal, and insertion configurations; select the appropriate mechanical style for maintenance and fan access. A duct-temperature result is velocity-weighted, so compare trends carefully against a single RTD. Build commissioning into the BAS using the actual model’s analog/digital transmitter and document pressure and damper/fan disturbances. Manufacturer material explicitly restricts which 116e variants support BACnet/Modbus, preventing the parent HTx116-P listing from promising these on every unit.

Original technical reference: Manufacturer model page, specification or data sheet. Verify the exact purchased suffix and revision, certificates and calibration assumptions.

AirAlign technical editorial enrichment · 25 October 2026. Published specs are not independent laboratory, hazardous-area certificate or active procurement signoff.